Guidelines For Performing Infrared Inspections Of Motor Control Centers

The Motor Control Centerprotection for motor in the same manner as a breaker.
The MCC enclosure protects personnel from contactInstead of opening contacts, fuses fail opening the
with current carrying devices, and it protects thecircuit. When overcurrent protection is provided by
components from various environmental conditions. It isfuses, a disconnect switch is required for manual
important that the enclosure is mounted to assureopening of the circuit. The disconnect switch and fuse
accessibility so that qualified personnel (such as ablock are typically one assembly. The hinge and blade
trained thermographer) can open the panel under load.connections on the switch are a typical source of
There are different classes and types of MCCs, butoverheating. High resistance from overuse or underuse
generally speaking, an MCC looks like a row of fileis usually the cause. Fuse clips are also a weak
cabinets with each cabinet representing an MCCconnection point for some disconnect designs.
section. The drawers of the file cabinet represent theDifferent types or manufacturers of fuses of the
plug-in units that contain the motor control components.same amperage may produce different thermal
Three phase power is distributed within the MCC bysignatures. While different size or amperage fuses will
bus bars, large metal current carrying bars. Thealso have a different thermal pattern, fuse bodies may
horizontal bus provides three-phase power distributionappear warmer than the rest of the circuit due to
from the main power supply. Vertical bus in eachconductor size.
section is connected from it to individual MCCs. BracingContactors
and isolation barriers are provided to protect againstStarters are made from two building blocks,
fault conditions. The plug-in units of an MCC havecontactors and overload protection. Contactors control
power stabs on the back to allow it to be plugged intothe electric current flow to the motor. Their function is
the vertical power bus bars of the structure.to repeatedly establish and interrupt an electrical
Beginning Your MCC Infrared Inspectionpower circuit. A contactor can stand on its own as a
Before opening the panel or door on a motor controller,power control device, or as part of a starter.
prescan the enclosure to assure a safe openingContactors operate electromechanically and use a
condition. If excessive heat appears on the surface ofsmall control current to open and close the circuit. The
the door, extra care should be taken when opening it.electromechanical components do the work, not the
The thermographer or escort may decide to note thehuman hand, as is the case with a knife blade switch
condition as unacceptable and not take a chance onor a manual controller. The sequence of operation of a
opening it under load. Once the unit is open, begin withcontactor is as follows: first, a control current is applied
both an infrared and a visual inspection to assure noto the coil; next, current flow into the coil creates a
dangerous conditions exist. Be systematic whilemagnetic field which magnetizes the E-frame making it
conducting the infrared inspection. Remember thean electromagnet; finally, the electromagnet draws the
system must be under load to conduct the inspection.armature towards it, closing the contacts. A contactor
Work from left to right or follow the circuit throughhas a life expectancy. If the contactor contacts are
carefully, inspecting all of the components. Look forfrequently opened and closed, it will shorten the life of
abnormal thermal patterns caused by high-resistancethe unit. As the contacts are exercised, an electrical
connections, overloads, or load imbalances. Inarc is created between the contacts. Arcs produce
three-phase systems this can be accomplished byheat, which can damage the contacts. Contacts
comparing phases. Adjust the level and span on theeventually become oxidized with a black deposit. This
infrared system to optimize the image. Properblack deposit may actually improve the electrical
adjustment will identify primary and secondaryconnection between the contacts by improving the
anomalies. The bus stabs and the connections to theseat, but burn marks, pitting, and corrosion indicate it is
main are important inspection points that are oftentime to replace the contacts. The following thermal
overlooked or misdiagnosed. The incoming connectionpatterns are associated with contactors. The coil of
to the main horizontal bus is usually located behind athe contactor is usually the warmest part of the unit.
cover or panel that is not hinged. These are typicallyHigh temperatures may indicate a breakdown of the
bolted connections and may have parallel feeders. Thecoil. Line side and load side lug connections may show
bus stab connections on the back of the plug-in unitshigh resistance heating from poor connections. Heating
are more difficult to inspect. The thermographer doesfrom burned and pitted contacts may be thermally
not have direct view of the connection, and the first"visible" on the body of the contactor.
indication of a problem can be seen on the incomingOverload Protection
conductors feeding the breaker or fused disconnect.The ideal motor overload protection is a unit with
Remember, even small temperature rises identified atcurrent sensing capabilities similar to the heating curve
this point could mean serious problems.of the motor. It would open the motor circuit when full
Motor Starters and Motor Controllersload current is exceeded. Operation of this device
The purpose of the motor starter is to protect thewould allow the motor to operate with harmless
motor, personnel, and associated equipment. Overtemporary overloads, but open up when an overload
90% of the motors used are AC induction motors, andlasts too long.
motor starters are used to start and stop them. ATypical thermal problems in overloads are found in the
more generic term would identify this piece ofconnections to the contactor, overload relay, or motor.
equipment as a motor controller. A controller mayThis protection can be provided by the use of an
include several functions, such as starting, stopping,overload relay. The overload relay limits the amount of
overcurrent protection, overload protection, reversing,current drawn to protect the motor from overheating.
and braking. The motor starter is selected to matchIt consists of a current sensing unit and a mechanism
the voltage and horsepower of the system. Otherto open the circuit. An overload relay is renewable and
factors used to select the starter include: motor speed,can work for repeated trip and reset cycles.
torque, full load current (FLC), service factor (SF), andOverloads, however, do not provide short circuit
time rating (10 or 20 seconds).protection. The melting alloy (or eutectic) overload relay
Understanding the thermal patterns of this equipment isconsists of a heater coil, a eutectic alloy, and a
critical to a successful inspection. Also correctlymechanical mechanism to activate a tripping device
identifying the source of the anomaly can makewhen an overload occurs. The relay measures the
recommendations more valuable.temperature of the motor by monitoring the amount of
Motors may be damaged or their life significantlycurrent being drawn. This is done indirectly through a
reduced if they operate continuously at a currentheater coil, which under overload conditions, melts a
above full load current. Motors are designed to handlespecial solder allowing a ratchet wheel to spin free and
in-rush or locked rotor currents without muchopen the contact. A bimetallic thermal overload uses a
temperature increase, providing there is a limitedU-shaped bimetal strip. In an overload condition heat will
duration and a limited number of starts. Overcurrentscause the bimetal to deflect and open a contact. The
up to locked rotor current are generally caused bysolid state overload relay does not generate heat to
mechanical overloading of the motor. The Nationalcause a trip. Instead, it measures current or a change
Electric Code (NEC) describes overcurrent protectionin resistance. The advantage of this method is that the
for this situation as "motor running overcurrentoverload relay doesn't waste energy generating heat
(overload) protection." This can be shortened toand doesn't add to the cooling requirements of the
overload protection. Overcurrents caused by shortpanel. Normal heating for an overload may look like a
circuits or ground faults are dramatically higher thanthermal anomaly. Heat generated in the coil or bimetal
those caused by mechanical overloads or excessivemay look like a connection problem. Typical thermal
starts. The NEC describes this type of overcurrentproblems in overloads are found in the connections to
protection as "motor branch-circuit short-circuit andthe contactor, overload relay, or motor.
ground-fault protection." This can be shortened toStarters
overcurrent protection. The four common varieties ofStarters are the combination of a controller, usually a
motor starters are: across-the-line, the reversingcontactor and an overload relay. The above
starter, the multispeed starter, and the reduced voltagedescriptions of the individual components apply to the
starter. Motor starters are generally comprised of thestarter systems. Reduced voltage starters are used in
same types of components. These include a breakerapplications that involve large horsepower motors.
or fused disconnect, contactor and overloads. ThereThey are used to reduce the in-rush current and limit
may also be additional components, including controlthe torque, and thus the mechanical stress on the load.
circuitry and a transformer. Understanding the thermalThe components of this type of starter should be
patterns of this equipment is critical to a successfulinspected as the motor steps up to speed. A separate
inspection. Also correctly identifying the source of thelow-voltage starter circuit is used to step the motor up
anomaly can make recommendations more valuable.to speed. Once at operating speed, these components
Overcurrent Protectionare de-energized.
NEC requires overcurrent protection and a means toCompleting Inspections
disconnect the motor and controller from line voltage.Remember that primary anomalies are the problems
Fused disconnects or thermal magnetic circuitthat readily stand out while secondary anomalies may
breakers are typically used for overcurrent protectionrequire that primary anomalies be adjusted into
and to provide a disconnect for the circuit. A circuitsaturation to allow for the identification of a secondary
breaker is defined in NEMA standards as a deviceanomaly. For example, different fuse types and sizes
designed to open and close a circuit by non-automaticwill cause different thermal signatures as will overload
means and to open the circuit automatically on arelays that are sized differently within the same circuit.
predetermined overcurrent without injury to itself whenAnomalies like this should be identified and reported.
properly applied within its rating. If we look at aAlso note that when evaluating the severity of a
cutaway of a breaker, we can identify potentialproblem, temperature is just one variable. All of the
connection problems. The line side and load side lugsparameters involved with the severity of the anomaly
are the most common source of abnormal heating, butshould be considered. To improve temperature
many breakers have a second set of boltedmeasurements, avoid low emissive surfaces. Look for
connections on the back of the breaker. Heat from thiscavity radiators or highly emissive insulation on
connection can be misdiagnosed as the main lug.conductors. Measure loads where component sizing,
There are also internal contacts where current flow isoverloading, or load imbalances are observed. Beware
interrupted by exercising the component. Theseof the effects of wind or convection on components.
contacts experience arcing each time the breaker isNote ambient temperatures, large thermal gradients,
opened. An arc is a discharge of electric currentand the source of heating. Safety should be the top
jumping across an air gap between two contacts.consideration.
Arcs are formed when the contacts of a circuitConclusion
breaker are opened under a load. Arcing under normalKnowing the equipment under inspection allows for the
loading is very small compared to an arc formed fromcorrect identification of problems that could be
a short circuit interruption. Arcing produces additionalmisdiagnosed or overlooked. Analyzing unfamiliar
heat and can damage the contact surfaces. Damagedthermal patterns on a component is easier when
contacts can cause resistive heating. Thermal patternsequipment design is reviewed. More precise repair
from these poor connections appear as diffuserecommendations can also be made. Locating
heating on the surface of the breaker. In addition, theretemperature differences qualitatively or quantitatively is
are several types of breakers that have internal coilsthe real benefit of infrared thermography. Knowing
used for circuit protection. These coils have heatwhere to look for these temperature differences
associated with them and can appear to be an internalcomes from knowledge of the equipment, and
heating problem, when in fact, it is a normal condition.knowledge of the equipment will make a better
Fused Disconnectsthermographer.
Fused disconnects are used to provide over-current