Welcome to your ultimate noise and vibration analysis resource!
 

Welcome to our Noise and Vibration Analysis Archive. Have fun browsing!

 

Article #2: Vibrations in cooling towers

(Browse for more articles)

 
Introduction PCS Potash New Brunswick continually being excited by vibrating
Division is a potash and salt mine near screens throughout the mill.
Sussex, N.B., a small farming community in High resolution spectra was taken at both
the southern part of the province. Potash the tower and vibrating screens to confirm
and salt are mined approximately 2000 feet that the exciting force at the towers is
below the surface. The salt requires coming from the vibrating screens in the
little processing and is used mainly for mill. The spectrum in Figure “2” taken
road salt. The potash is hoisted to at the cooling tower indicates a dominant
surface where it goes through a frequency of 197 c.p.m. By comparing this
concentrator. to the dominant frequency in Figure
There it has all the impurities removed “3” of 198 c.p.m., which represents
and is sized to the needs of customers all the output r.p.m. of the Vibrating
across the world. Potash is mainly used in Screens, confirms that the exciting force
the fertilizer industry, being one of the at the cooling towers is coming from the
three main ingredients. vibrating screens operating in the mill.
Cooling towers are required to remove heat Over the years, several false vibration
from the water that has been used to cool alarms have come in at the control center
many different systems throughout the showing severe vibration at the cooling
mill. The water travels in an endless towers, when in actual fact it was the
loop, from all the systems and then back building vibration that had increased.
to the tower where the heat is removed and Figure “4” is a trend comparing mill
back to the same systems. Basically, after vibration to actual fan vibration. The
the cooling water has been used to remove building continually vibrates at 197
any excess heat from any system, it is c.p.m. which is much higher than the 1x
pumped to the roof of the mill where the fan vibration.
cooling tower is situated. The water is Unfortunately, this causes many false
pumped into the top of the tower; an area alarms at the control room. This is a good
called a distribution basin (hot water example why band alarming is extremely
side). The basin has metering orifices useful in an online vibration monitoring
that allow even distribution of the water system. A highpass filter to filter out
over the fill. the low end background noise would also be
The fill acts like a radiator in a car. an asset. A filter in this application
On top of the cooling tower, there is a would also increase the dB range of the
large fan that draws the air through the system so that there would be less
fill, cooling the water and exhausting the attenuation at the high end of the FFT. In
hot air to atmosphere. After the water has the control room, we only alarm on
traveled through the fill, it reaches the velocity because displacement is too
cold water basin at the bottom of the sensitive to low frequency vibration.
tower where it drains by gravity back into However, there is a data collector
a holding tank in the mill. From there it interface at the signal conditioning rack
is pumped to all the different systems to plug into with a data collector. This
before heading back to the tower once allows the collection of spectrums and
again. The efficiency of the tower is waveforms while performing routine data
measured by the temperature differential collection or whenever there could be a
between the hot water and cold water problem arising. Having this ability
basin. Algae, dirt, scale, leaves and allowed us to head off at least a couple
organic growth are some of the solids if problems before a major failure may have
allowed to build up that can plug the occurred. The first problem was spotted
fill. The water is treated to help prevent after noting that the 1x vibration at fan
some of this from occurring. speed had increased (Fig. “5”).
Case History Cooling Towers are Although, a 1x vibration is usually the
categorized under critical equipment in first indication of unbalance, that was
our plant. A catastrophic failure of a not the problem. It was during the early
cooling tower has the potential to summer when the vibration level increased.
partially shut a major portion of the site The cooling tower was shut down to allow
down, costing thousands of dollars in lost us and the mechanics to do an inspection,
production. which revealed major cracks in the gearbox
It is very important that we know the base. The cracking was severe enough that
mechanical condition of our cooling towers the gearbox was flexing a fair amount,
at all times. especially at high speed. Severe corrosion
Unfortunately, that was not always the was the main cause of the problem. If
case. Monitoring Cooling Towers at the allowed to go undetected, this could very
site has changed drastically over the well have lead to a significant failure.
years. At the beginning, vibration After welding up the cracks, the amplitude
monitoring consisted of mechanical ball/ at 1x returned very close to normal.
spring vibration cut-off switches mounted A second problem that showed up at 1x the
several feet from any actual drive input shaft speed was also detected.
equipment. This type of switch would not Through routine data collection, it was
detect any initial mechanical fault in the noted that the frequency at 1x input shaft
drive train until a potentially disastrous speed had increased dramatically in
failure was about to occur. amplitude with multiple harmonics (Fig.
Examples of these faults were motor 6). Again, the tower was shutdown to allow
bearing defects, bearing and gear defects for an inspection. A suggestion was made
in the gearbox, loose bolts, and drive to the mechanics to give the jackshaft a
shaft problems. The whole tower had to be close check because it was felt there was
in a spin before this type of vibration looseness showing up in the drive train
monitoring would detect a problem. Later, that was directly related to the input
walk around data collection was started, speed. This remark headed the mechanics in
but we were only able to access the motor the right direction, as they quickly noted
and not the gearbox. This type of that the jackshaft coupling inserts were
monitoring is okay for periodic checks on completely worn out. This was causing
the motor but not acceptable for looseness in the drive shaft. Most of the
continuous monitoring of the complete rubber was completely missing on a couple
power train. In the mill standard of the inserts. After replacing the
accelerometers are utilized for online inserts and doing a laser alignment, the
monitoring on the fans. These vibration levels returned to normal.
accelerometers were mounted on the We also experienced vibration problems
gearboxes of the cooling towers. after a major overhaul of the cooling
Cooling Tower fans have certain aspects towers. PCV honeycomb fill was replaced
that makes them stand apart from other and new style fan blades installed because
rotating equipment. they were not cooling to acceptable
1. Combination of both slow turning and standards. The new blades are hollow, made
normal running speeds. from fiberglass and shaped very similar to
2. Harsh environment. an airplane propeller.
3. Structural rigidity problems. They are more efficient than the original
4. Gearmesh defects. blades, as they move more air with fewer
It is important to use a transducer on the horsepower. After the job was completed,
gearbox that will effectively measure fan both tower fans had to be balanced. The
speed up through various gearmesh tower structure has weakened over the
frequencies. With this requirement and years because of normal aging and being
recommendations from the Cooling Tower weighted down with sludge in the fill.
Institute, velocity pickups were The tower swings back and forth with
installed. Unbalance should be the most little restriction because of less
common fault, which is usually measured in dampening in the system. Unfortunately,
displacement. We only wanted to integrate this causes the overall vibration level to
once (basic rule of vibration) so that is increase. It is necessary to have the
what tipped the scale towards the velocity unbalance force down to a minimum. Fig.
pickup. Since that decision was made a lot “7” is a multiple spectra display
of research and development has gone into showing the results of the balance job.
accelerometers. The unbalance force went from 11 mils to 2
The accelerometers on the market today are mils. At an operating speed of 324 rpm,
very capable of giving reliable data on this level of vibration is considered very
both slow and high-speed equipment. good.
Another advantage is the size of an Conclusions 1. If your online vibration
accelerometer compared to velocity monitoring systems are limited to only
transducers when mounting on smaller overall alarming, it would be beneficial
equipment. to look at a method to plug into it with
After mounting velocity transducers (IRD your vibration analyzers. Without the
580) on the reducers and having the signal ability to collect spectra and waveforms,
sent directly to the control room for there is a good chance of missing certain
monitoring, everyone felt more comfortable faults in the drive train. This could lead
that they were getting closer to some real to unscheduled downtime and possibly a
online monitoring. The control room was catastrophic failure. There had been
able to get a velocity and displacement instances when fan blades have
overall readings from the velocity disintegrated due to blade fatigue,
transducers. One major restriction that we causing serious damage to the tower and
do have with our present online system is endangering lives. There are excellent
the inability to generate any spectrums or monitoring systems on the market today,
band alarming from our control room. but unfortunately industry has been slow
Again, all the control room receives is an adapting.
overall vibration signal. This is totally 2. Another PDM tool that should be used on
inadequate for truly effective machine monitoring cooling tower gearboxes is oil
condition monitoring. This, in our case analysis. Trending the different elements
can be very problematic because at times in the oil has proven to be an affective
the overall vibration level at the cooling way of giving early warning detection of
towers can be relatively high. bearing and gear failures in any oil
The tower is supported on a steel lubricated drive systems. Oil analysis
structure on top of the roof approximately integrates well with vibration analysis.
225 feet off the ground, making it a 3. It should be noted that walk around
natural cantilever. The building sways data collection can be very effective but
back and forth at 198 c.p.m., (fig. you have to be aware of its limitations,
“2”) and the towers being on the top in certain areas it just cannot replace a
of the building are exposed to the bulk of good online system.
this vibration. The building vibration is






1- A- B- C- D- 2- 3- 4- 5- 6- 7- 8- 9- 10- 11- 12- 13- 14- 15- 16- 17- 18- 19- 20- 21- 22- 23- 24- 25- 26- 27- 28- 29- 30- 31- 32- 33- 34- 35- 36- 37- 38- 39- 40- 41- 42- 43- 44-